276
submitted 6 months ago by Brkdncr@lemmy.world to c/technology@lemmy.world

Title reads like at ad, but this is a new way to reach energy independence. I actually have a small EcoFlow device and it’s pretty good for the price.

I hope this tech can be made available in the US soon.

you are viewing a single comment's thread
view the rest of the comments
[-] Sleepkever@lemm.ee 3 points 5 months ago

The breaker only sees the current flowing through the breaker though. Not the additional current provided by the solar panels since those don't flow through the breaker. So it will pop later then that the cables are rated for, therefore introducing an overheat and fire hazard.

[-] Brkdncr@lemmy.world 1 points 5 months ago

Maybe for a same-circuit device that’s consuming more than the breaker can provide? I don’t know enough about this tech but would expect this can be accounted for in some way.

[-] Sleepkever@lemm.ee 1 points 5 months ago

There are ways to somewhat fix it for circuits with a single use.

Fixing the same example: A 16A breaker for the solar feed in, a single 16A breaker for all the consuming appliances on that circuit. And another 16A breaker on the feed in for that circuit is an example that is sometimes used in the Netherlands to add a feed in to an existing circuit with a single outlet connected to it. Meant for washingmachines for instance.

This ensures that the circuit on all circumstances has a maximum current of 16A flowing over any wire by also measuring the outgoing current of both feed in circuits. But if you have multiple outlets you'd still need to stiol measure at a single place or use low enough breakers per outlet that the total stays below the 16A. Which the UK might have if I recall correctly.

Then again this is not a normal setup and requires change in the electric circuit of the home. Which most consumers won't even realize. Like I said, if everyone keeps to the fine print this thing probably has and limits the extra plug-in solar panels to 1 per circuit, it's unlikely to actually cause issues because of overdimensioning of the wires. And the safety margin built in which is likely how they have gotten approval. But ignoring or not reading that text and plugging multiple in on the same circuit can and will cause a fire hazard with heavy consumers on the same circuit.

this post was submitted on 25 May 2024
276 points (100.0% liked)

Technology

59554 readers
2721 users here now

This is a most excellent place for technology news and articles.


Our Rules


  1. Follow the lemmy.world rules.
  2. Only tech related content.
  3. Be excellent to each another!
  4. Mod approved content bots can post up to 10 articles per day.
  5. Threads asking for personal tech support may be deleted.
  6. Politics threads may be removed.
  7. No memes allowed as posts, OK to post as comments.
  8. Only approved bots from the list below, to ask if your bot can be added please contact us.
  9. Check for duplicates before posting, duplicates may be removed

Approved Bots


founded 1 year ago
MODERATORS